Extremely flexible for extremely large cooling systems: Controller AEGIS X
AEGIS X is a controller for treating cooling water in cooling towers and boilers.
In order to optimise the cooling process and prevent biological growth, deposits and corrosion, the controller continuously monitors the electrolytic conductivity and controls bleeding. Biocide metering based on time or measured values prevents contamination in the cooling tower.
With up to two satellite units, AEGIS X monitors and controls several cooling towers at the same time. The combination of main and satellite unit ensures truly excellent flexibility. This makes the controller perfectly suited to large cooling systems with many parameters, including corrosion.
Thanks to the large number of communication options, the cooling tower can be remotely controlled with ease. An individually adaptable web server A web server is a software application executed by the DULCOMARIN® II. more in the glossary makes simple management, tracking and data visualisation possible.
Your benefits
- Up to two satellite units can be added for additional inputs and outputs, allowing more sensors and pumps to be connected.
- Intuitive operation via the HMI (Human-Machine Interface) thanks to a clearly legible industrial display and robust keys for standard commands, such as calibration and monitoring.
- The adaptable web server permits simple configuration of process settings as well as monitoring and visualisation of process data.
- Extensive overview and control of the cooling tower processes: All process data and alarms can be communicated to the process control system via fieldbuses such as Modbus RTU.
- Advanced communication options: Various network protocols such as FTP or MQTT enable remote access and data management via Wi-Fi and LAN (Ethernet).
- Advanced calculations, such as cost calculation for managing chemicals.
Technical Details
Comprehensive inputs and outputs
- Up to 24 flexible sensor inputs and mA outputs (8 per device), e.g. CTFS sensor, linear polarisation resistor (LPR) corrosion sensor
- Up to 30 output relays and pulse outputs (10 per device) to control pumps and other actuators
- Up to 24 digital inputs (8 per device) to control level switches, water meters and remote switches
- Up to 12 pulse frequency outputs
- Up to 18 relays
Communication options
- In-built Modbus RTU and via gateways (BACnet, Modbus TCP, PROFINET)
- Web interface via Wi-Fi and Ethernet, FTP server, rest API, MQTT client interface. The client interface is an intuitive remote control via a Wi-Fi or network connection to your PC or smartphone, e.g. for configuration settings or setpoint settings
Technical Data
|
Measured variables and measuring ranges | Conductivity: with the digital sensor CTFS: 0.1 - 10 mS/cm Via conductivity module L3 depending on sensor used (LMP, LFT): 50 μS cm - 20 mS/cm Via mA module AA with the inductive conductivity sensor ICT: 8 to 2 mS/cm, 20 mS/cm, 200 mS/cm Type of connection mV: pH: 0.00 ... 14.00 ORP potential: -1500 ... +1500 mV Type of connection mA (amperometric measured variables, measuring ranges corresponding to sensors, 2 ppm, 10 ppm): Chlorine Chlorine dioxide Chlorite Bromine Ozone Hydrogen peroxide Peracetic acid Temperature: via Pt 100/Pt 1000, measuring range 0 ... 150 °C |
Inputs and outputs | Inputs 4 plug-in module slots per unit for 2-channel serial sensor input module 2-channel conductivity input module 2-channel mV input module 2-channel mV/mA input module 2-channel mA input module Outputs 2-channel mA output module 6 output relays as changeover contacts, of which 3 are potential-free and 3 are AC/DC 4 pulse frequency outputs for controlling metering pumps 8 digital control inputs for contact water meter, flow switch and pause for locking |
Resolution | pH: 0.01 pH ORP: 1 mV Amperometric analysis (chlorine etc.): 0.001/0.01 ppm, 0.01 vol. % |
Accuracy | 0.3% based on the full-scale reading |
Temperature compensation | Pt 100/Pt 1000 for pH |
Control characteristic | P/PI/PID control |
Electrical Connection | 100 – 230 V, 50/60 Hz |
Ambient temperature | -5 … 50 °C at max. 95% relative air humidity (non-condensing) |
Tests and approvals | CE, MET, UK CA |
Housing material | PC with flameproofing equipment |
Dimensions | 276 x 424 x 137 mm (H x W x D) |
Enclosure rating | Wall-mounted: IP 67 |
Field bus connection | Modbus RTU, additional field buses via gateway |